Share

Raychem

RAYCHEM
Tech Self-regulating Power-limiting Constant wattage
Cable BTV QTVR XTV KTV VPL FMT / FHT
Max maintain T 65°C 110°C 121°C 150°C 230°C 230°C
Max exposure T 85°C 110°C 250°C 250°C 260°C 260°C
T-class T6 T4 T3/T2 T2 By design By design
Max circuit length < 200m < 115m < 245m < 230m < 450m < 330m
Max power output at 10°C < 30W/m < 64W/m < 63W/m < 65W/m < 61W/m < 40W/m
Nominal voltage 230V AC 230V AC 230V AC 230V AC 230V, 400V AC 230V, 400V AC